Leave Your Message

description2

Product introduction

It is suitable for cleaning and disinfecting medical instruments, utensils and articles in hospital supply disinfection center, supporting ultrasonic cleaning machine, steam water for pressure steam sterilizer, etc. The water produced meets the cleaning and disinfection specifications of WS310-2016 supply room, with electrical conductivity < 5μs/cm(raw water TDS≤300ppm).

  • Hospital reverse osmosis pure water treatment system (4)7lm
  • Hospital reverse osmosis pure water treatment system (3)5w6
  • Hospital reverse osmosis pure water treatment system (2)vw7
  • Hospital reverse osmosis pure water treatment system (1)xe8

Application

Hospital supply clean and disinfection department.
Supply Clean and Disinfection Pure Water System

Technical Features

1. Fully automatic operation without special care.
2.RO film automatic pulse flushing function.4. The main machine adopts open plastic sprayed carbon steel structure, withuniversal wheel at the bottom.
5. Modular design, water production can be upgraded.
6. Automatic protection function of raw water shortage, overload and overcurrent.
7. Water leakage protection.
SSY-CG

Model

Capacity

Power

Input Power

Overall Size

SSY-CG-500L

500L/H

2.2KW

AC220V/50Hz

1600*750*1650mm

SSY-CG-750-1000-1500L

750/1000/1500L/H

3KW/4KW

AC380V/50HZ

1600*750*1650mm

SSY-CG-2000L

2000L/H

10KW

AC380V/50HZ

1200*750*1650mm

SSY-CG-3000-6000L

Customized

Technical Parameter

Raw Water Requirement:

Urban tap water,TDS≤300ppm

Environment Temperature:

5-45℃

Raw Water Pressure:

0.2-0.4Mpa

Productive Water Quality:

conductivity:<5μs/cm@25℃

Water quality meets WS310-2016 Supply room cleaning and disinfection specifications

Remark:

The water capacity decreases about 3% when the temperature drops by 1℃.

Hospital reverse osmosis pure water treatment systemfw3

SSY-CG Process Flow Diagram

Raw water → raw water tank → raw water pump → sand tank → carbon tank → softening tank → salt tank → security filter → high pressure pump →Reverse osmosis membrane → pure water tank → conveying pump → water point


Leave Your Message