Leave Your Message

description2

SSY-CD Reverse Osmosis Pure Water System

Product Introduction

Endoscopy center is an important place for endoscopy and treatment of digestive system, which provides an important scientific basis for the diagnosis of clinical digestive system diseases.
Quality of water produced: Water quality meets WS507-2016 soft endoscope cleaning and disinfection technical specifications, total bacteria ≤10cfu/100mL(raw water TDS≤300ppm).
Application: Endoscopic cleaning pure water equipment is suitable for Xinhua, Laoken, Jianghan, Kunshan, Qianying, White elephant, Meimei, Kengwang and other hospitals endoscopic cleaning equipment supporting pure water.
  • CD-reverse-osmosis-pure-water-systemb8n
  • CD-reverse-osmosis-PURE-WATER--systemd3w

Technical Features

1. Membrane automatic cleaning technology,automatic online flushing RO membrane, prevent membrane scaling, prolong the service life of the membrane.
2. PLC intelligent man-machine control system,convenient operation, real-time monitoring equipment operation information.
3. Automatic multistage pretreatment system, effectively remove impurities, reduce residual chlorine hardness.
4. Modular design, easy to maintain later, expand capacity.
5. Online high-precision monitoring instrument, real-time online display of water quality, pressure, flow and other information.
6. Circulating disinfection and sterilization, with invention patents and utility model patents circulating disinfection and sterilization process.
7. Fully automatic operation, a variety of intelligent protection functions, no need for special duty.
8. Water leakage protection, automatic water leakage detection sensor, water leakage in time to cut off water.

Model

Capacity

Power

Input Power

Overall Size

SSY-CD-500L

500L/H

2.2KW

AC220V/50HZ

1200*700*1660mm

SSY-CD-750L-1500L

750L/1000L/1500L/H

3/4KW

AC380V/50HZ

1600*750*1660mm

SSY-CD-2000L

2000L/H

10KW

AC380V/50HZ

1200*750*1660mm

SSY-CD-3000L-6000L

Customized

Technical Parameter

Model:

SSY-CD-500/750/1000/1500/2000L/H

Capacity:

500/750/1000/1500/2000L/H

Environment Temperature:

5-45℃

Raw Water Pressure:

0.2-0.4Mpa

Productive Water Quality Index:

RO Conductivity<15μs/cm@25℃;Total Bacteria ≤10cfu/100ml

Bacterial Removal Rate≥99.6%  Particle (>0.2μm) <1 piece/ml

Ion Retention Rate:97%-99%    Organic matter retention rate>99%

It meets the technical specification of WS507-2016 soft endoscope cleaning and disinfection.

Application:

hospitals endoscopic cleaning equipment

SSY-CD Process Flow Diagram

Raw water → Raw water pump → Quartz sand tank → Activated carbon tank → softening tank → Salt tank → Precision filter → High pressure pump → Reverse osmosis membrane → Pure water tank→ Delivery pump → Water point


Leave Your Message